An Electrical Installation Condition Report (EICR) is a formal inspection of a building’s fixed wiring by a qualified electrician, and the core EICR requirements in England are straightforward: private landlords have had to obtain one at least every five years since 2020, a 2025 amendment brought social housing providers under the same duty, and non-compliance can cost up to £30,000 per breach.1GOV.UK. Electrical Safety Standards in the Private and Social Rented Sectors – Guidance2Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 Commercial premises and owner-occupied homes sit outside the specific 2020 Regulations but can still need one for other reasons.
Who Is Legally Required to Have One
Private Landlords
The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 apply to any tenancy where the tenant occupies the property as their only or main residence and pays rent. For new tenancies, the inspection must be complete before the tenancy begins. For tenancies already running when the rules took effect, the deadline for a first inspection was 1 April 2021.3Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 – Regulation 3
Social Housing Providers
A 2025 amendment extended the same regime to the social rented sector. Housing associations and council landlords must now have both the electrical installations and any electrical equipment they supply inspected and tested by a qualified person at least every five years.1GOV.UK. Electrical Safety Standards in the Private and Social Rented Sectors – Guidance
Commercial Premises
Commercial property is not covered by the 2020 Regulations. Instead, the Health and Safety at Work Act 1974 places a general workplace-safety duty on employers,4Legislation.gov.uk. Health and Safety at Work etc Act 1974 and the Electricity at Work Regulations 1989 require all electrical systems to be maintained so they do not give rise to danger.5Legislation.gov.uk. The Electricity at Work Regulations 1989 Neither uses the term “EICR,” but the Health and Safety Executive treats electrical maintenance as a core employer responsibility, and periodic inspection is the standard way to evidence compliance.6Health and Safety Executive. Electricity and the Law
Homeowners
Owner-occupiers have no statutory duty to obtain an EICR. Mortgage lenders and insurers sometimes ask for one, particularly on older properties, and it is worth considering before major renovation or when buying a home whose wiring has not been assessed in years.
How Often You Need One
For rented properties covered by the 2020 Regulations, the maximum interval is five years. The catch: if the inspector’s report specifies a shorter interval, that shorter interval becomes the legal deadline.3Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 – Regulation 3 Five years is a ceiling, not a default.
Commercial and specialist premises have no single statutory interval. IET Guidance Note 3 publishes recommended maximum intervals for different environments:7The Institution of Engineering and Technology. Periodic Inspection or Planned Maintenance
- Swimming pools, launderettes, petrol filling stations, and caravan parks: 1 year
- Cinemas: 1 to 3 years
- Theatres, leisure complexes, and places of public entertainment: 3 years
- Restaurants, hotels, and public houses: 5 years
The pattern tracks how hard the environment is on wiring. Moisture, heavy footfall, and constant use accelerate wear, so a pool’s electrics are checked far more often than a restaurant’s.
What the Report Codes Mean
An EICR classifies any issues found using standard codes, and those codes decide whether the report is satisfactory.
- C1 (Danger Present): immediate risk of injury. The inspector will usually make it safe on the spot. Any C1 makes the overall report unsatisfactory.
- C2 (Potentially Dangerous): not immediately dangerous but could become so. Remedial work is required, and a C2 makes the report unsatisfactory.
- C3 (Improvement Recommended): the installation is safe but could be brought up to the current edition of BS 7671. Advisory only.
- FI (Further Investigation): something could not be fully assessed and needs additional testing. The report stays unsatisfactory until that is done.
The line most landlords miss is between C2 and C3. A C3 is a suggestion. A C2 is a legal obligation. Ignoring C2 or FI findings puts a landlord in breach of the regulations.
Deadlines After the Inspection
Once the report is issued, the clock starts on three separate deadlines. Existing tenants must get a copy within 28 days. New tenants must get a copy before they move in. If the local housing authority makes a written request for the report, the landlord has 7 days to supply it.3Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 – Regulation 3
Where the report is unsatisfactory, any urgent remedial or investigative work identified must be completed within 28 days, or sooner if the report itself specifies a shorter deadline. The landlord must then obtain written confirmation from the electrician who did the work and pass a copy to both the tenant and, where applicable, the local authority.2Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020
Twenty-eight days is tighter than it sounds once you factor in finding an available electrician, scheduling the visit, and getting the paperwork back. Leaving it to the last week is where landlords tend to miss the deadline.
Penalties and Council Enforcement
Where a landlord breaches the regulations, the local housing authority must serve a remedial notice setting out the required action and giving the landlord 28 days to comply.8Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 – Part 3 If nothing changes, the authority can send an authorised person into the property to carry out the work, provided the tenant consents, with the cost billed back to the landlord.
On top of that, the authority can impose a financial penalty of up to £30,000.2Legislation.gov.uk. The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 That figure is a ceiling rather than a standard fine. Authorities weigh the severity of the breach, any prior non-compliance, and whether the landlord attempted to put things right. Even a lower-value penalty creates a record that can complicate future licensing applications and insurance renewals.
Who Can Carry Out the Inspection
The regulations require a “qualified person.” In practice, that means an electrician who holds current registration with a competent person scheme such as NICEIC or NAPIT. Registration verifies training and insurance, and confirms the electrician works to BS 7671, the national standard for electrical installations.9BSI. BS 7671 – Requirements for Electrical Installations Before booking, check the electrician’s registration number on the scheme’s online register. A report from someone outside a competent person scheme may not be accepted by the local authority and offers little protection if enforcement action follows.
Preparing for the Visit and What It Costs
A standard residential EICR takes a few hours. The inspector needs unobstructed access to the consumer unit, every socket, every light fitting, and any other fixed electrical point, so move furniture and clear storage in advance. Gather any earlier EICRs, Electrical Installation Certificates, or Minor Works Certificates you hold, along with anything you know about the age of the wiring or when it was last upgraded.
Circuits will be switched off individually during testing, causing short interruptions to power. Flag anything that cannot tolerate power loss, such as medical equipment, aquarium heaters, or an alarm system without battery backup, so the inspector can work around it.
For a typical UK home, EICR prices generally run between £120 and £350, with smaller flats at the lower end and larger houses at the top. Commercial inspections cost more because of the number of circuits involved and can reach several thousand pounds for larger buildings. Those figures cover the inspection and report only. If C1 or C2 issues turn up, remedial work is priced separately and depends entirely on what needs fixing. Ask for a written breakdown of any repair quote before authorising the work.